Technical information

An example of a steam quantity calculation

The following example and table provides guidance for such calculations. The guide-line values for the necessary amount of steam are based on the amount of outside air being fed in cubic metres per hour at a room temperature of + 22° C and an ambient air temperature of + 0° C and -15° C respectively.

  • Eg. Desired relative humidity=40%
  • Amount of air fed= 1500 m³/hour
  • Ambient air temperature= -15° C
  • Quantity of steam = 1500x6,6=9 900 grams/hour or 9.9 kg/hour

The table is based on a water content of about 2 g/kg air at + 0° C and about 1g/kg air at -15° C.

 